6 CONTACTS – CIRCUIT BREAKER ANALYZER – CB14

Ref : CB14

The CB14 is a 6 contacts circuit breaker analyzer designed to perform Timing, Motion as well as Static & Dynamic Resistance Measurement (DRM) in a single test. It also includes 3 multifunction analog inputs.

It can be used on all types of circuit breakers typically found in electrical substations, going from the distribution level all the way to high voltage levels.

Our CB14 has been designed to use the same software as our CBV and to perform the same tests as our CBA, hence being the best complement to both those instruments.

While the CBA is focused on large circuit breakers and the CBV on vibro-acoustic technology, the CB14 is the perfect solution for testing small circuit breakers easily, at an affordable price and still with the best precision.

If you already own a CBA/CBV, all CBA/CBV accessories already purchased can be used with the CB14! the only thing you need to care about is the size of the breakers you are about to test!

OpenZen Software

OpenZen is an all-in-one software that includes all the necessary tools for testing, processing, calculating and results analysing in the field or in the laboratory.

KEY FEATURES

    • Instrument with a life expectancy better than 15 years. Waterproof & Impact resistant
    • Timing, Motion, Dynamic Resistance Measurement in a single test
    • All CBA/CBV accessories can be used with the CB14
    • Simple graphic environment with the extensive analysis thanks to many tools such as superposing signals from different tests, scaling, zooming…
    • Extensive calculation capabilities
    • Light, Complete & Complete instrument for professionals on the field
  • Sampling time: 5 microseconds to 26 milliseconds
  • Sampling rate: 38Hz to 200kHz
  • Recording time: 10 milliseconds to 30 minutes
  • Resolution: 16 bits A/D converter
  • Accuracy: +/- 1mV
  • Command Outputs/Current Inputs: 2
  • Contacts: 6
  • Vibration (Accelerometers) Inputs: 0
  • Multipurpose Analogs Inputs (+– 10V): 3
  • Digital Optical/Magnetic Encoders: 1
  • AC/DC voltage detection (up to 300 volts): 2